LES-A
LES-A specifically designed for use with HID light units such as High Pressure Sodium, Metal Halide and Fluorescent Lamps.

Description

LES-A (Analyser) is a 3 phase 4 wire advanced microprocessor controlled energy saving controller, ready for installation and wiring.
LES-A specifically designed for use with HID light units such as High Pressure Sodium, Metal Halide and Fluorescent Lamps.

Features

Totally self-contained microprocessor control.
Under voltage protection.
Series Security Contactor (secure the magnetic Coil from over heating)
Requires no changes to customers existing lighting.
Provides up to 25% reduction in Energy Cost.
Built-in Manual Bypass facility.
No Harmonic Distortion (pure Sine Wave Output).
More than 98 % Efficient.
Increases lamp life by up to 300%.
CE Approved

Ranges

LES-A-30A 400V 3 phase 4 wire   27Amps per phase
Dimensions: 500mm W x 400mm H x 200mm D 50Kgs
LES-A-50A 400V 3 phase 4 wire   45Amps per phase
Dimensions: 700mm W x 550mm H x 250mm D 75Kgs
LES-A-80A 400V 3 phase 4 wire   72Amps per phase
Dimensions: 700mm W x 550mm H x 270mm D 75Kgs
LES-A-100A 400V 3 phase 4 wire 90Amps per phase
Dimensions: 700mm W x 550mm H x 270mm D 80Kgs
LES-A-125A 400V 3 phase 4 wire 112Amps per phase
Dimensions: 1000mm W x 700mm H x 350mm D 90Kgs

Technical Specification

Input voltage Nominal 400V (3x230V+N)
Control Voltage 230VAC+10%
Output voltage equal to input voltage Without energy saving state
Output voltage Equal to Input Voltage - ∆V
Voltage reduction ∆V Equal to 25V or 20V
Frequency 50-60Hz
Energy saving 25%  (for 25V reduction) or  20% (for 20V reduction)
Adjustable minimum input voltage 250V -200V   (pot. On face plate)
Light Protection Under voltage protection  Manual By Pass
Electrical Insulation 2.5kV
Cabinet protection IP20 standard
Cables access Installation Bottom access standard
Ambient temp. 0°C to +50°C
Standard CE, approval
Communications protocol Optional RS232, RS485 (option)
Communication with information centre Include GSM modem for control, monitoring and reporting (option)

Operating Principle

After the power is supplied to the controller and if the 'ON' command exists, the controller supplies full voltage to the system.
Providing the 'Energy Saving' contact is enabled, the programmed delay time will commence, which is fixed at approximately 6 minutes.
After the timer expires the LES-A is in 'Energy Saving' mode and the output voltage is reduced by approximately 25V or 20V according the customer requirement and order (e.g. if the input voltage is 232V, the output voltage will be 207V).  
In the case of power failure, after the power returns (restart), and all the control signals ('ON' & 'Energy Saving') are still present, the controller provides full voltage to the system and energy saving will begins after the time delay as mentioned above.
If, during energy saving mode, it becomes necessary to restart some or all lamps, this can be achieved by opening the connection to terminals 3 & 4 (disable 'Energy Saving' mode).
The unit will now supply full voltage until the 'Energy Saving' mode is again enabled via terminals 3 & 4 and the timer has elapsed.

Energy & Power Analyzer Multimeter

The Power Analyzer Multimeter is a compact, multi functional, three-phase multimeter, especially designed to suit the needs of power and energy measurement in electric panel.
The Power  Analyzer Multimeter includes an open protocol communication for, Building management systems. It is designed for power and energy metering, as well as quality power measurement and data logging.
The Power Analyzer Multimeter is capable of measuring active, reactive and apparent power, as well as frequency, power factor, current, voltage, harmonics analysis and has a waveform graphic display.

The Power Analyzer Multimeter‘s state of the art graphic LCD enables multilingual graphic display data and analysis.

Main Features

  1. Measurements accuracy according to international standard IEC 687/61036.
  2. Accuracy better than 0.1% - Class 0.1.
  3. Power quality analysis according to British standard EN50160.
  4. Max’ and Min’ measuring: Volts, Amperes, Powers, frequencies and P.F.
  5. Power High demand (KVA and KW) measuring.
  6. Multilingual simply operated menus.
  7. Energy data logging.
  8. Serial communication Via RS-485 Open protocol such as MODBUS
  9. State of the art graphic LCD display  128X64 resolution.
  10. Simple installation.

Measurements accuracy:

The Power Analyzer Multimeter has an autonomic measuring unit, which ensures accuracy of the power energy metering according to the international standard IEC 687/61036. Each cycle is being sampled 1600 times.
The measurement accuracy of energy and energy components such as current, voltage, power and power factor is better than 0.1%.

Power Quality Analysis:

Harmonic disturbances and bad power factor can cause a massive damage to the electric facilities.
The Power Analyzer Multimeter enables monitoring & analysing the supplied electricity quality  to the facility.
The Power Analyzer Multimeter also measures true power factor, which includes the influences of the harmonics disturbances. The Harmonics spectrum analysis (up to the 31’th) can be displayed on the LCD. 


 





Add Your Comment

Call me!
New Events
The International Energy Saving Seminar.
The three days training course is an intensive, interactive, Marketing, Sales, hands-on training on how to
Light Energy Seminar
Light Energy saving Seminar
Ekotec Ltd. Vintec’s New Business Partner
Ekotec has obtained exclusive rights to market a unique lighting control system in Poland.

 

New Articles
CO2 emission calculation
A website calculates the CO2 emission
Lighting Energy consumptions markets in the UK
One of the main sectors in the commercial lighting markets is that of Street lighting
Effect of the Voltage Level
Light energy saver often inspires questions relating to effects on lamp and fitting life


MashooMashoo - Build Website - Promote Website